摘要:为给某城市110KV多电源网络进行继电保护设计,首先对电网进行短路电流计算,包括最大、最小运行方式下的正序、零序电流的短路计算,对各个继电器的动作值进行整定。在过电流保护不满足的情况下,相间故障选择距离保护,接地故障选择零序电流保护,同时对距离保护、零序电流保护进行整定计算,并用AutoCAD绘制出保护原理图、电网接线示意图、简化电路图,由于电压等级比较高,线路长,为保护整个电网的安全、稳定运行还对电网的自动重合闸做来选择。通过短路计算,同时对距离保护、零序电流保护进行整定计算,最终绘制出保护原理图。
关键词:多电源网络;继电保护;短路电流;整定计算
Abstract:For a city of 110KV power network relay protection design, the power system short-circuit current calculation, including maximum, minimum operation mode of positive, zero sequence current of short circuit calculation, the relay operation value setting. The overcurrent protection does not satisfy the condition, fault distance protection, grounding fault selection of zero sequence current protection, at the same time to distance protection, zero-sequence current protection setting calculation, using AutoCAD draw protection diagram, network wiring diagram, simplified circuit, because the voltage grade is relatively high, long route, for the protection of the whole power grid safe and stable operation, but also to power grid automatic reclosing to choose. Through the short circuit calculation, at the same time to distance protection, zero sequence current protection setting calculation, the final draw protection diagram.
Key words: power network;relay protection;setting calculation;short circuit current
随着电力系统的飞速发展,继电保护技术得天独厚,在40余年的时间里完成了发展的4个历史阶段:继电保护的萌芽期、晶体管继电保护、集成运算放大器的集成电路保护和计算机继电保护。电力系统的运行中最常见也是最危险的故障是发生各种形式的各种短路。发生短路时可能会产生以下后果:
(1)电力系统电压大幅度下降,广大用户负荷的正常工作遭到破坏。
(2) 故障处有很大的短路电流,产生的电弧会烧坏电气设备。
(3)电气设备中流过强大的电流产生的发热和电动力,使设备的寿命减少,甚至遭到破坏。
(4)破坏发电机的并列运行的稳定性,引起电力系统震荡甚至使整个系统失去稳定而解列瓦解。
因此在电力系统中要求采取各种措施消除或减少发生事故的可能性,一旦发生故障,必须迅速而有选择性的切除故障,且切除故障的时间常常要求在很短的时间内(十分之几或百分之几秒)。实践证明只有在每个元件上装设保护装置才有可能完成这个要求,而这种装置在目前使用的大多数是由单个继电器或继电器及其附属设备的组合构成的,因此称为继电保护装置,它能够反应电力系统中电气元件发生故障或不正常运行状态,并动作于断路器跳闸或发生告警信号。